Installation of Parquet Floors
1)
Job Site Inspection
2) Storage and Handling
3) Subfloor Requirements
4) General Information on Adhesives
5)
Spreading the Adhesive
6)
Installing the Parquet Flooring
7)
Completing the Installation
8)
Sanding
9)
Stain and Finish
10)
Maintenance
Installer/Owner Responsibility
Back
to main F.A.Q. |
|
| PRE-INSTALLATION
PROCEDURES |
1)
JOB SITE INSPECTION
- The building should be closed in with
all outside doors and windows in place. All concrete, masonry,
framing members, drywall, paint and other "wet" work should
be thoroughly dry.
- The wall coverings should be in place
and the painting completed except for the final coat on
the base molding. When possible, delay installation of base
molding until flooring installation is complete.
- Exterior grading should be complete with
surface drainage directing water away from the building.
All gutters and downspouts should be in place.
- Solid oak parquet may be installed on
or above grade level only. Do not install in full bathrooms.
- Basements and crawl spaces must be dry
and well ventilated.
- Crawl space must be a minimum of 24"
(600 mm) from the ground to underside of joists. A ground
cover of 6-8 mil black polyethylene film is essential as
a vapor barrier with joints lapped six inches and taped.
The crawl space should have perimeter venting equal to a
minimum of 1.5% of the crawl space square footage. These
vents should be properly located to foster cross ventilation.
- Subfloor must be checked for moisture
content using the appropriate testing method.
Wooden subfloor moisture reading must not exceed 12% and differential between the flooring and subfloor must be less than 4%.
- Permanent air conditioning and heating
systems should be in place and operational. The installation
site should have a consistent room temperature of 65-75°
F and humidity of 40-60% for 14 days prior, during and until
occupied, to allow for proper acclimation.
|
|
| |
2)
STORAGE AND HANDLING
Handle and unload with care. Store
in a dry place being sure to provide at least a four-inch
air space under cartons which are stored upon "on-grade" concrete
floors. Flooring should not be delivered until the building
has been closed in with windows and doors in place and until
cement work, plastering and all other "wet" work is completed
and dry. Concrete should be at least 60 days old. Solid oak
parquet flooring should be stored in the environment in which
it is expected to perform. Air conditioning/heating systems
should be in place and in operation at least 14 days prior,
during and after installation of the flooring. Check adhesive
label for storage limitations. |
|
3)
SUBFLOOR REQUIREMENTS
For best results and adhesion, Czar Floors recommends
installing 1/4" Luan plywood underlayment over existing
subfloor. Installing vapor barrier (asphalt saturated paper)
between subfloor and underlayment will help to keep moisture
away from the wood floor. This is especially important for
the ground and below ground level floors. Standard 4 X 8 plywood
sheet should be cut in four pieces and screwed to subfloor,
leaving a 1/8" gap between the sheets to allow for expansion.
SUBFLOORS MUST BE:
- CLEAN - Scrape, broom
clean, and smooth. Free of wax, paint, oil, sealers, adhesives,
curing agents and other debris.
- LEVEL/FLAT - Within
3/16" in 10' and/or 1/8" in 6'. Sand high areas or joints,
fill low areas (no more than 1/8" at a time) with a cementitous
leveling compound or milk additive latex patch of 3,000
PSI minimum compressive strength. Follow the instructions
of the leveling compound manufacturer. Leveling compounds
must be tested for moisture to ensure they are properly
cured and within the manufacturer's specified requirements
for proper installation.
- STRUCTURALLY SOUND -
Nail or screw any loose areas that squeak. Replace any water-damaged,
swollen or delaminated subflooring or underlayment. Avoid
subfloor with excessive vertical movement unless they have
been properly stiffened prior to the installation of the
wood flooring.
- DRY - Check moisture
content of the subfloor with a reliable moisture meter.
RECOMMENDED SUBFLOOR SURFACES
- PREFERRED: ¾" (19 mm) CDX grade
plywood
- ¾" (23/32") OSB PS2 rated underlayment
- MINIMUM: 5/8" CDX grade plywood
- Concrete slabs
- Ceramic, terrazzo, slate and marble
- Acoustic concrete
- Cork (Acoustic)
- Vinyl, resilient tile, cork flooring
- Metal
- Existing solid wood flooring
- ¾" chip, waferboard, particle board
- CONCRETE SLABS. Solid parquet flooring can be glued
directly to concrete. Do not use a concrete sealer nor install
over one. Surface preparation using mechanical methods such
as sanding or scouring with open coat paper or a titanium
disk is preferred. The concrete must be of high compressive
strength. All concrete subfloors should be tested for moisture
content. Visual checks are not reliable. Acceptable test
methods for subfloor moisture content include:
NOTE: Test several
areas, especially near exterior walls and walls containing
plumbing.
- A 3% Phenolphthalein in Anhydrous
alcohol solution. Chip the concrete at least ¼" deep (do
not apply directly to the concrete surface) and apply several
drops of the solution to the chipped area. If any color
change occurs, further testing is required.
- Calcium Chloride test. The maximum
moisture transfer must not exceed 3 lbs./1000 square feet
with this test.
- Tramex Concrete Moisture Encounter
meter. Moisture readings should not exceed 4.5 on the upper
scale.
NOTE: A "DRY" SLAB, AS
DEFINED BY THESE TESTS CAN BE WET AT OTHER TIMES OF THE YEAR.
THESE TESTS DO NOT GUARANTEE A DRY SLAB. ALL CONCRETE SLABS
SHOULD HAVE A MINIMUM OF 6 MIL POLY FILM MOISTURE BARRIER
BETWEEN THE GROUND AND THE CONCRETE.
WOOD SUBFLOORS & WOOD STRUCTURAL
PANEL SUBFLOORS
- Plywood: Must be APA
grade rated sheathing or CDX minimum.
- Oriented Strand Board (OSB):
Must be PS2 rated installed sealed side down.
- Particleboard: Must
be a minimum 40-LB density, stamped underlayment grade and
¾" thick.
- Make sure existing floor or subfloor
is dry and well nailed or screwed down every 6" along each
joist to avoid squeaking or popping before the floor is
installed. The wood subfloor must not exceed 12% moisture
content. Measure moisture content of both subfloor and wood
flooring to determine proper moisture content with a reliable
wood moisture meter. The difference between the moisture
content of the wood subfloor and the wood flooring must
not exceed 4%. Optimum performance of hardwood floor covering
products occurs when there is no horizontal or vertical
movement of the subfloor.
- All underlayment panels should
be spaced 1/8" apart to insure adequate expansion space.
This can be achieved by using a circular saw set at the
depth of the underlayment and cutting around the perimeter
of the panel. Do not install over existing glue-down wood
floors. Do not install over nailed floors that exceed 3-¼"
in width. Wide width floors must be overlaid with plywood.
When installing over existing wood floors parallel with
the flooring, it may be necessary to install an additional
¼" layer of plywood to stabilize the flooring or install
the wood floor at right angles.
RADIANT HEATED SUBFLOORS
- System must be operational and heated
for at least 7 days prior to beginning installation.
- Turn off heat and let subfloor cool
down to room temperature 3-4 hours prior to starting
the job.
- Radiant heated floors must be temperature
controlled or engineered for the R-rating of the floor
covering product installed upon them. BEFORE installation
begins, ascertain that the system is designed and controlled
for wood flooring. Failure to do so may cause excessive
heat damage and shrinkage. Install floor per the application
instructions.
- After installation, turn system
back on immediately to its normal room temperature setting.
The subfloor surface must not exceed 85° F throughout
the life of the floor.
- It is recommended to use Rift/Quartered sawn material for the radian heat applications for the best results.
|
|
|
4) GENERAL
INFORMATION ON ADHESIVES
NOTE:
When installing UNFINISHED SOLID WOOD PARQUET flooring, allow
a minimum of 36 hours adhesive curing time before applying
seals, stains and finishes to unfinished flooring. Trowel
filling and fillers are required to reduce the possibility
of panalization caused by the finish "gluing" the slats together.
Test the moisture content of the wood in accordance with the
stain/finish manufacturer's recommendations. Avoid installing
from the surface of the flooring. If necessary distribute
weight using a kneeler board.
Maximum Adhesive Working Times:
- Urethane Adhesive - 60 minutes (Always
read container label before proceeding)
- Polymeric Resin Adhesive - 90 minutes
(Always read container label before proceeding)
- Open times and curing times of ALL adhesives
vary dependant upon subfloor porosity, air movement, humidity
and room temperature. Urethane adhesive has a shortened
work time in high humidity environments whereas polymeric
resin adhesive working time will be lengthened. In areas
of low humidity, open time will be longer with urethanes
and shorter with polymeric resins. Adjust the amount of
adhesive spread accordingly. The adhesive should not be
applied if subfloor or room temperature is below 65° F (20°
C).
- Spread sufficient amounts of recommended
adhesive with the recommended trowel (figure below) in an
area that can be covered in 60-90 minutes.

Hold the
trowel at a minimum 45° angle (figure below) firmly against
the subfloor to obtain a 50-60 sq. ft. per gallon spread rate.

- When not in use, keep the adhesive container
tightly closed to prevent thickening. Thickening of the
adhesive will cause difficulty in spreading the adhesive.
- Proper ventilation within the room must
be provided. An electric fan is helpful.
Please follow technical
specification for working time for adhesive.
Czar Floors recommends Bostik's
Best
adhesive. Simply, it's one of the best out there. Expensive,
but well worth it to avoid installation failure. It's a urethane
with a tenacious grip.
Bostik Best glue is the only adhesive tested and certified by Czar Floors. Use other adhesives at your own risk. Czar Floors does not provide warranty on subfloor separation for other adhesives. |
|
| INSTALLATION |
| |
5)
SPREADING THE ADHESIVE
NOTE: Clean adhesive from
the surface of the floor frequently using the recommended
adhesive cleaner. Use clean towel, changed frequently, to
prevent haze and adhesive residue. |
|
| |
6)
INSTALLING THE PARQUET FLOORING
- It may help to dry lay the section of
the floor first to get an idea. This is especially helpful
with artistic parquet. Use drawings as your reference.
- Immediately lay the floor tiles on the
newly spread adhesive. DO NOT lay the floor tiles on dry
adhesive (Always lay the floor tiles on wet adhesive). If
the adhesive becomes too dry, scrape up the old adhesive
and spread more. Installing on wet adhesive eliminates rolling
the floor with a heavy roller. The working time for the
adhesive is 60-90 minutes. Working time will vary depending
on the job site conditions. IMPORTANT: Stand or kneel on
the subfloor during the installation to avoid shifting the
tiles. NOTE: Slightly slide tile diagonally about 1"
back and forth to insure good adhesive spread. Tile can
be temporarily secured with finishing nails.
- PROPER PLACEMENT OF THE FIRST FLOOR TILE
IS THE KEY TO THE ENTIRE INSTALLATION. Carefully place a
parquet tile at the intersection of the two chalk lines.
Straight plank boards can be used to align and secure the
tiles as shown in the picture below.
Start at the center of the room in one of the quadrants using chalk lines and temporary boards as a guide.
- Continue laying the balance of the floor
tiles along the starting quadrant. Align each floor tile
squarely.
- Do not push or shove the floor tiles
too strenuously as this could cause the first and second
floor tiles to move. Simply realign them and proceed with
the installation.
Use pieces of wide blue masking tape to temporarily hold the tiles in place to avoid "floating" of the tile in still wet adhesive. This tape can removed after glue is cured or sanded off.
- Avoid hammering or forcing the floor
tiles together as this will destroy the built-in expansion
spaces and may destroy the squareness of the floor tile.
You may use a rubber mallet to tap the tiles.
- After laying the floor tiles across the
first starting area, trim the last floor tiles as needed
to obtain the proper ½" expansion space next to the walls.
Use a small band or saber saw for final trimming. Firmly
secure each floor tile when cutting with a saber saw.
- During the installation, occasionally
remove a piece of flooring from the subfloor and inspect
the back for proper adhesive transfer. Adequate adhesive
transfer is necessary to ensure sufficient holding strength.
DO NOT REMOVE PROTECTIVE PLASTIC TAPE ON THE TILE SURFACE.
It will be removed during first pass sanding.
For medallion installation
follow this link: Medallion
Installation Instructions
If installing flooring medallion,
install parquet tiles without glue in this area. The medallion shape
can be outlined first on the subfloor and then marked on the parquet
using the template.
|
|
| |
7)
COMPLETING THE INSTALLATION
- When the starting area has been completed,
including cutting to the wall, proceed to the second laying
area.
- The second laying area is quite simple
as you now have sufficient floor tiles installed to resist
floor tile movement.
- Again, cut the last floor tiles to allow
a ½" expansion space from the end wall.
- Proceed by laying other areas,
repeating the installation procedure of the starting area.
Trim out each laying area before proceeding to the next
area.
- Maintain the ½" expansion space around
the perimeter of the room and around all fixed objects.
- Avoid pressing heavily or stepping on
the recently laid floor tile as this may destroy the ridging
of the adhesive and positioning of the tile.
- Fill the
expansion gap along the wall with silicone.
Cork
can be placed in the required perimeter expansion space
to support the flooring at the walls. This specialized cork,
with a very resilient binding resin, acts as a compression
spring. It should be cut in small pieces to fit snugly between
walls and each unit of parquet. If cork is not used, gaps
near the walls of the room may develop. Since there is nothing
to push the parquet back as it dries during the heating
season, these gaps will be larger than normal gaps as seasonal
drying occurs.
- Allow a minimum of 36 hours drying time
before moving furniture or walking on the newly laid parquet
floor.
- It is normal to have some gaps between
tiles and wood pieces after this phase. Use quality wood
patches and Full-Trowel Fillers to cover those gaps. Full-Trowel
Filler is thinner than Wood Patch, and designed to spread
across the surface of the wood floor. Just pour a workable
puddle and trowel the floor, going back and forth across
the cracks and voids to ensure deep penetration, removing
excess filler as you go. 3 1/2-gallon pail fills up to 3,000
square feet.
|
|
| |
| 8) SANDING
Use a drum sander to remove
plastic tape from the surface. Three sandings with progressively
finer paper is recommended. The final cut should be a rotary
sander. Pay attention if several different woods used in the parquet as softer woods may sand faster then harder species and may develop uneven surface. |
|
| |
9) STAIN AND
FINISH
Polyurethane or wax finish
can be applied. Two coats of fast drying sealer can be applied
before final coat. Consider water-based finishes
made by Bona. Read descriptions for Bona finishes: Traffic and Mega . |
|
| |
10) MAINTENANCE
Vacuum as often as you would your carpet.
Brush between parquet tiles. If wax used for finish, periodically
buff the floor using paste wax.
It is very important to maintain humidity level in the 40 to 60% range. Use portable or HVAC built-in humidifiers during the heating season. |
|
| |
For general hardwood floor question,s
please check the excellent NOFMA
(The Wood Flooring Manufacturers Association ) Web site. Another
great source for information is NWFA
(National Wood Flooring Association). Czar Floors is a proud
member of this organization.
INSTALLER/OWNER RESPONSIBILITY
Beautiful hardwood floors
are a product of nature and therefore, not perfect. Our wood
floors are manufactured in accordance with accepted industry
standards, which permit a defect tolerance not to exceed 5%.
The defects may be of a manufacturing or natural type.
- The installer assumes all responsibility
for final inspection of product quality. This inspection
of all flooring should be done before installation. Carefully
examine flooring for color, finish and quality before installing
it. If material is not acceptable, do not install it and
contact us immediately.
- Prior to installation of any hardwood-flooring
product, the installer must determine that the job-site
environment and the sub-surfaces involved meet or exceed
all applicable standards and recommendations of the construction
and materials industries. These instructions recommend that
the construction and subfloor be dry, stiff and flat. The
manufacturer declines any responsibility for job failure
resulting from or associated with sub-surface or job-site
environment deficiencies.
- Prior to installation, the installer/owner
has final inspection responsibility as to grade, manufacture
and factory finish. The installer must use reasonable selectivity
and hold out or cut off pieces with defects, whatever the
cause.
- Use of stain, filler or putty stick for
defect correction during installation should be accepted
as normal procedure.
- When flooring is ordered, 5% to 7% must
be added to the actual square footage needed for cutting
and grading allowance.
- Should an individual piece be doubtful
as to grade, manufacture or factory finish, the installer
should not use the piece.
- Use of appropriate products for correcting
subfloor voids should be accepted as a normal industry practice.
|
|
|
|